5.2 Sys – System
5.2.1
Sys: Direct Controls
Sys . Rst. Err. LED [Operation / Reset]
False False, True
╚═▷ True or not true
P.1
Direct Command to acknowledge a (device-internal) error. This also resets the System (Ready/Error) LED.
Sys . User Restart [Service / General]
False False, True
╚═▷ True or not true
P.1
Direct Command to manually initiate a warm restart of the device.
Sys . Factory Reset [Service / General]
False False, True
╚═▷ True or not true
P.1
Direct Command to reset all settings of the device to their respective default.
Sys . Force Backup Prot. [Service / General]
False False, True
╚═▷ True or not true
P.1
Direct Command to manually force the device into the Backup Protection mode. This disables all other protection,
supervision and communication functions, so that it makes sense only for testing purposes (e.g. for testing Backup
Protection during commissioning).
5.2.2
Sys: Values
Sys . Op. Hours [Operation / Count and RevData / WIC1]
Device operation hours counter, that shows for how long the device has been operating since the last restart.
Sys . Build [Device Para / Version / WIC1]
[Device Para / Version / DiggiMEC]
Build Number
Sys . DM version [Device Para / Version / WIC1]
Version of the device model
27WIC1WIC1-2.0-EN-REF
5 System
5.2 Sys – System

Table of Contents

Other manuals for Seg WI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Seg WI Series and is the answer not in the manual?

Seg WI Series Specifications

General IconGeneral
BrandSeg
ModelWI Series
CategoryRelays
LanguageEnglish

Related product manuals