Position Indication, Part 3: Current-Based and One Contact
Switchgear
wiProtGeneral_Y36
10
Prot . Pos ON
11
Prot . Pos OFF
30
[Aux ON]
Prot .
I ON
IL1
IL2
IL3
Φ
max
&
&
If: »Prot . Meth.Detect.Bkr.Pos.« = “Current and Aux”
And: »Prot . Aux ON« = “DI 1”
And: »Prot . Aux OFF« = “no assignment”
Fig. 48: “Close” / Aux ON position (52a) indication via current measurement and Digital input
(with “Open” / Aux OFF position (52b) being derived from this).
Switchgear
wiProtGeneral_Y37
10
Prot . Pos ON
11
Prot . Pos OFF
Prot .
I ON
IL1
IL2
IL3
Φ
max
&
&
31
[Aux OFF]
If: »Prot . Meth.Detect.Bkr.Pos.« = “Current and Aux”
And: »Prot . Aux OFF« = “DI 2”
And: »Prot . Aux ON« = “no assignment”
Fig. 49: “Open” / Aux OFF position (52b) indication via current measurement and Digital input
(with “Close” / Aux ON position (52a) being derived from this).
Position Indication, Part 4: Two Contacts
Switchgear
wiProtGeneral_Y46
30
[Aux ON]
31
[Aux OFF]
10
Prot . Pos ON
&
11
Prot . Pos OFF
&
If: »Prot . Meth.Detect.Bkr.Pos.« = “Aux-Based”
And: »Prot . Aux ON« = “DI 1”
And: »Prot . Aux OFF« = “DI 2”
Fig. 50: “Close” / Aux ON (52a) and “Open” / Aux OFF position (52b) via two Digital Inputs.
134 WIC1 WIC1-1.0-EN-MAN
4 Protective Elements
4.1.4.1 Switchgear Conguration