Behaviour of the Fault Recorder
The Fault Recorder is triggered by the rising edge of the »Prot . Pickup« (General Pickup)
signal. (Note that »Prot . Pickup« (General Pickup) is an OR-connection of all pickup signals,
see ╚═▷ “4.1 »Prot« – General Protection Module”.) (Since the General Pickup signal
triggers the Fault Recorder one can say that the 󰊟rst protection pickup triggers the Fault
Recorder.) The Fault Recorder is not triggered by functions that have been con󰊟gured
as »De󰅰nition« = “Alarm” (see ╚═▷ “De󰊟nition (“Alarm ↔ Trip”) of a Protection Function).
If the (General) Pickup is followed by a (general) Trip (signal »Prot . Trip«) then the Fault
Recorder updates all data. In this case all values describe the fault situation at the moment
of the trip.
178 WIC1 WIC1-1.0-EN-MAN
5 Fault Recorder