11.2.3.2.5.2 Very Inverse [VINV] (IEEE C37.112)
»Char« = “IEEE VINV”
0.5
1
2
5
10
15
0.01 0.1 1 10 100
0.1
1
10
100
1000
t / s
I2 / I> (multiples of pickup)
tChar=
wiNPSDOC_Z06
Fig. 109: VINV: reset delay (left half, I2 < I
2>
) and trip delay (right half, I2 > I
2>
), example for
I
Dyn.Lim.
= 20⋅I
2>
.
See ╚═▷ “Explanation for All Characteristics (»I2>«)” and ╚═▷ “11.2.3.2 Inverse-Time
Characteristics (»I2>«)” for details.
Reset Delay
Various reset modes are available: Resetting via characteristic, delayed and instantaneous.
Trip Delay
If I
2>
< I2 < I
Dyn.Lim.
, the trip delay is de󰊟ned by the characteristic.
For I2 > I
Dyn.Lim.
, the trip delay t is kept constant at t = t
Dyn.Lim.
.
322 WIC1 WIC1-1.0-EN-MAN