3.8.1.4 Latching of a DiggiMEC-LED with an Assigned Trip Signal
Special case: Whenever a trip signal is assigned to a LEDx, the corresponding pickup
signal gets assigned as well, with the following behavior:
When the corresponding pickup signal occurs, the LEDx starts blinking.
With latching, this continues until a reset is done or until the assigned trip signal
occurs. (Reset: See ╚═▷ “2.11 Reset”.)
When the assigned trip signal occurs, the LEDx is lit.
With latching, this continues until a reset is done. (Reset: See ╚═▷ “2.11 Reset”.)
Moreover, there is the following additional behavior with latching:
When a pickup – without a trip – occurs and drops o󰊞 again, the LEDx starts 󰊠ashing
(with 󰊠ashing pattern OFF : ON ≈ 10 : 1).
LEDs
wiLED_Y01
Settings:
DiggiMEC . LED2 assign. = I> . Trip
DiggiMEC . LED2 latching = No latching
I> . Trip
I> . Pickup
Reset
DiggiMEC-LED 2:
WIC1-Trip-LED:
DiggiMEC-LEDs
wiLED_Y02
Settings:
DiggiMEC . LED2 assign. = I> . Trip
DiggiMEC . LED2 latching = With latching
I> . Trip
I> . Pickup
Reset
WIC1-Trip-LED:
DiggiMEC-LED 2:
98 WIC1 WIC1-1.0-EN-MAN
3 Hardware
3.8.1.4 Latching of a DiggiMEC-LED with an Assigned Trip Signal

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Seg WIC1-3 and is the answer not in the manual?

Seg WIC1-3 Specifications

General IconGeneral
BrandSeg
ModelWIC1-3
CategoryRelays
LanguageEnglish

Related product manuals