Schweitzer Engineering Laboratories, Inc. SEL-487E-3, -4 Data Sheet
27
220 Vac: Pickup 150.3–264 Vac rms;
Dropout <93.2 Vac rms
250 Vac: Pickup 170.6–300 Vac rms;
Dropout <106 Vac rms
Communications Ports
EIA-232: 1 Front and 3 Rear
Serial Data Speed: 300–57600 bps
Communications Card Slot for Optional Ethernet Card
Ordering Options: 10/100BASE-T
Connector Type: RJ45
Ordering Option: 100BASE-FX Fiber-Optic
Connector Type: LC
Fiber Type: Multimode
Wavelength: 1300 nm
Source: LED
Min. TX Power: –19 dBm
Max. TX Power: –14 dBm
RX Sensitivity: –32 dBm
Sys. Gain: 13 dB
Communications Ports for Optional TiDL (EtherCAT) Interface
EtherCAT Fiber-Optic Ports: 8
Data Rate: Automatic
Connector Type: LC fiber
Protocols: Dedicated EtherCAT
Class 1 LASER/LED
Wavelength: 1300 nm
Fiber Type: Multimode
Link Budget: 11 dB
Min. TX Power: –20 dBm
Min. RX Sensitivity: –31 dBm
Fiber Size: 50–200 m
Approximate Range: 2 km
Data Rate: 100 Mbps
Typical Fiber Attenuation: –2 dB/km
Time Inputs
IRIG Time Input—Serial Port 1
Input: Demodulated IRIG-B
Rated I/O Voltage: 5 Vdc
Operational Voltage Range: 0–8 Vdc
Logic High Threshold: 2.8 Vdc
Logic Low Threshold: 0.8 Vdc
Input Impedance: 2.5 k
IRIG-B Input—BNC Connector
Input: Demodulated IRIG-B
Rated I/O Voltage: 5 Vdc
Operational Voltage Range: 0–8 Vdc
Logic High Threshold: 2.2 Vdc
Logic Low Threshold: 0.8 Vdc
Input Impedance: >1 k
Dielectric Test Voltage: 0.5 kVac
PTP—Ethernet Port 5A, 5B
Input: IEEE 1588 PTPv2
Profiles: Default, C37.238-2011 (Power Profile),
IEC/IEEE 61850-9-3-2016 (Power
Utility Automation Profile)
Synchronization Accuracy: ±100 ns @ 1-second synchronization
intervals when communicating directly
with master clock
Operating Temperature
–40° to +85°C (–40° to +185°F)
Note: LCD contrast impaired for temperatures below –20° and above +70°C
Humidity
5% to 95% without condensation
Weight (Maximum)
4U Rack Unit (TiDL
[EtherCAT] only): 6.4 kg (14.1 lb)
5U Rack Unit: 13.2 kg (29.2 lb)
6U Rack Unit: 15.1 kg (33.3 lb)
7U Rack Unit: 16.4 kg (36.2 lb)
Terminal Connections
Rear Screw-Terminal Tightening Torque, #8 Ring Lug
Minimum:
Maximum:
1.0 Nm (9 in-lb)
2.0 Nm (18 in-lb)
User terminals and stranded copper wire should have a minimum
temperature rating of 105°C. Ring terminals are recommended.
Wire Sizes and Insulation
Wire sizes for grounding (earthing), current, voltage, and contact
connections are dictated by the terminal blocks and expected load
currents. You can use the following table as a guide in selecting wire
sizes. The grounding conductor should be as short as possible and sized
equal to or greater than any other conductor connected to the device,
unless otherwise required by local or national wiring regulations.
Type Tests
Installation Requirements
Overvoltage Category: 2
Pollution Degree: 2
Safety
Product Standards IEC 60255-27:2013
IEEE C37.90-2005
21 CFR 1040.10
Dielectric Strength: IEC 60255-27:2013, Section 10.6.4.3
2.5 kVac, 50/60 Hz for 1 min: Analog
Inputs, Contact Outputs, Digital Inputs
3.6 kVdc for 1 min: Power Supply,
Battery Monitors
2.2 kVdc for 1 min: IRIG-B
1.1 kVdc for 1 min: Ethernet
Connection Type Min. Wire Size Max. Wire Size
Grounding (Earthing)
Connection
14 AWG (2.5 mm
2
)N/A
Current Connection 16 AWG (1.5 mm
2
) 10 AWG (5.3 mm
2
)
Potential (Voltage)
Connection
18 AWG (0.8 mm
2
) 14 AWG (2.5 mm
2
)
Contact I/O 18 AWG (0.8 mm
2
) 10 AWG (5.3 mm
2
)
Other Connection 18 AWG (0.8 mm
2
) 10 AWG (5.3 mm
2
)