SEL-487E-3, -4 Data Sheet Schweitzer Engineering Laboratories, Inc.
28
Impulse Withstand: IEC 60255-27:2013, Section 10.6.4.2
IEEE C37.90-2005
Common Mode:
±1.0 kV: Ethernet
±2.5 kV: IRIG-B
±5.0 kV: All other ports
Differential Mode:
0 kV: Analog Inputs, Ethernet,
IRIG-B, Digital Inputs
±5.0 kV: Standard Contact Outputs,
Power Supply Battery Monitors
+5.0 kV: Hybrid Contact Outputs
Insulation Resistance: IEC 60255-27:2013, Section 10.6.4.4
>100 M @ 500 Vdc
Protective Bonding: IEC 60255-27:2013, Section 10.6.4.5.2
<0.1 @ 12 Vdc, 30 A for 1 min
Object Penetration: IEC 60529:2001 + CRGD:2003
Protection Class: IP30
Max Temperature of Parts
and Materials: IEC 60255-27:2013, Section 7.3
Flammability of Insulating
Materials:
IEC 60255-27:2013, Section 7.6
Compliant
Electromagnetic (EMC) Immunity
Product Standards: IEC 60255-26:2013
IEC 60255-27:2013
IEEE C37.90-2005
Surge Withstand Capability
(SWC):
IEC 61000-4-18:2006 + A:2010
IEEE C37.90.1-2012
Slow Damped Oscillatory, Common and
Differential Mode:
±1.0 kV
±2.5 kV
Fast Transient, Common and Differential
Mode:
±4.0 kV
Electrostatic Discharge
(ESD):
IEC 61000-4-2:2008
IEEE C37.90.3-2001
Contact:
±8 kV
Air Discharge:
±15 kV
Radiated RF Immunity: IEEE C37.90.2-2004
IEC 61000-4-3:2006 + A1:2007 +
A2:2010
20 V/m (>35 V/m, 80% AM, 1 kHz)
Sweep: 80 MHz to 1 GHz
Spot: 80, 160, 450, 900 MHz
10 V/m (>15 V/m, 80% AM, 1 kHz)
Sweep: 80 MHz to 1 GHz
Sweep: 1.4 GHz to 2.7 GHz
Spot: 80, 160, 380, 450, 900, 1850,
2150 MHz
Electrical Fast Transient
Burst (EFTB):
IEC 61000-4-4:2012
Zone A:
±2 kV: Communication ports
±4 kV: All other ports
Surge Immunity: IEC 61000-4-5:2005
Zone A:
±2 kV
L-L
±4 kV
L-E
±4 kV: communication ports (Ethernet
and IRIG-B)
Note: Cables connected to EIA-232
communications ports shall be less than
10 m in length for Zone A compliance.
Zone B:
±2 kV: communication ports (except
Ethernet and IRIG-B)
Note: Cables connected to EIA-232
communications ports shall be less than
10 m in length for Zone B compliance.
Conducted Immunity: IEC 61000-4-6:2013
20 V/m; (>35 V/m, 80% AM, 1 kHz)
Sweep: 150 kHz–80 MHz
Spot: 27, 68 MHz
Power Frequency Immunity
(DC Inputs):
IEC 61000-4-16:2015
Zone A:
Differential: 150 V
RMS
Common Mode: 300 V
RMS
Power Frequency Magnetic
Field:
IEC 61000-4-8:2009
Level 5:
100 A/m; 60 Seconds; 50/60 Hz
1000 A/m 1 to 3 Seconds; 50/60 Hz
Note: 50G1P 0.05 (ESS = N, 1, 2)
50G1P 0.1 (ESS = 3, 4)
Power Supply Immunity: IEC 61000-4-11:2004
IEC 61000-4-17:1999/A1:2001/A2:2008
IEC 61000-4-29:2000
AC Dips & Interruptions
Ripple on DC Power Input
DC Dips & Interruptions
Gradual Shutdown/Startup (DC only)
Discharge of Capacitors
Slow Ramp Down/Up
Reverse Polarity (DC only)
Damped Oscillatory
Magnetic Field:
IEC 61000-4-10:2016
Level 5:
100 A/m
EMC Compatibility
Product Standards: IEC 60255-26:2013
Emissions: IEC 60255-26:2013, Section 7.1
Class A
47 CFR Part 15B
Class A
Canada ICES-001 (A) / NMB-001 (A)
Environmental
Product Standards: IEC 60255-27:2013
Cold, Operational: IEC 60068-2-1:2007
Test Ad: 16 hours at –40°C
Cold, Storage: IEC 60068-2-1:2007
Test Ad: 16 hours at –40°C
Dry Heat, Operational: IEC 60068-2-2:2007
Test Bd: 16 hours at +85°C
Dry Heat, Storage: IEC 60068-2-2:2007
Test Bd: 16 hours at +85°C
Damp Heat, Cyclic: IEC 60068-2-30:2005
Test Db: +25 °C to +55°C, 6 cycles (12 +
12-hour cycle), 95% RH
Damp Heat, Steady State: IEC 60068-2-78:2013
Severity: 93% RH, +40°C, 10 days
Cyclic Temperature: IEC 60068-2-14:2009
Test Nb: –40°C to +80°C, 5 cycles
Vibration Resistance: IEC 60255-21-1:1988
Class 2 Endurance, Class 2 Response
Shock Resistance: IEC 60255-21-2:1988
Class 1 Shock Withstand, Class 1 Bump
Withstand, Class 2 Shock Response
Seismic: IEC 60255-21-3:1993
Class 2 Quake Response
Reporting Functions
High-Resolution Data
Rate: 8000 samples/second
4000 samples/second
2000 samples/second
1000 samples/second
Output Format: Binary COMTRADE
Note: Per IEEE C37.111-1999 and IEEE C37.111-2013, Common Format for
Transient Data Exchange (COMTRADE) for Power Systems.