Schweitzer Engineering Laboratories, Inc. SEL-487E-3, -4 Data Sheet
3
➤
Software-Invertible Polarities. Inverting individual or grouped CT and PT polarities allows you to account for
field wiring or zones of protection changes. CEV files and all metering and protection logic use the inverted polarities,
whereas COMTRADE event reports do not use inverted polarities but rather record signals as applied to the relay.
➤ Parallel Redundancy Protocol (PRP). PRP provides seamless recovery from any single Ethernet network failure.
The Ethernet network and all traffic are fully duplicated with both copies operating in parallel.
➤ IEC 61850 Operating Modes. The relay supports IEC 61850 standard operating modes such as Test, Blocked,
On, and Off.
➤ IEEE 1588, Precision Time Protocol (PTP). PTP provides high-accuracy timing over an Ethernet network.
➤ Digital Relay-to-Relay Communications. MIRRORED BITS communications can monitor internal element conditions
between bays within a station, or between stations, using SEL fiber-optic transceivers. Send digital, analog, and
virtual terminal data over the same M
IRRORED BITS channel.
➤ Sequential Events Recorder (SER). The SER records the last 1000 events, including setting changes, startups,
and selectable logic elements.
➤ Oscillography and Event Reporting. The relay records voltages, currents, and internal logic points at a sampling
rate as fast as 8 kHz. Offline phasor and harmonic-analysis features allow investigation of bay and system
performance. Time-tag binary COMTRADE event reports with high-accuracy time stamping for accuracy better
than 10 s.
➤ Digitally Signed Upgrades. The relay supports upgrading the relay firmware with a digitally signed upgrade file.
The digitally signed portion of the upgrade file helps ensure firmware and device authenticity after it is sent over a
serial or Ethernet connection.
➤ Increased Security. The relay divides control and settings into seven relay access levels; the relay has separate
breaker, protection, automation, and output access levels, among others. Set unique passwords for each access level.
➤ Rules-Based Settings Editor. You can communicate with and set the relay by using an ASCII terminal or use
QuickSet to configure the relay and analyze fault records with relay element response. Use as many as 200 aliases
to rename any digital or analog quantity in the relay.