45
Appendix D: Specifications
APPENDIX D: SPECIFICATIONS
ALERT ZONES
Number of Zones: 6
Zone Connector: terminal block
;POF5ZQFT/0/$DPOUBDU,5IFSNJTUPS¡UP'UP$"OE,5IFSNJTUPS
(-87° to 168°F; -66° to 76°C), and 4-20mA (-80,000.0 to 80,000.0
Zone Characteristics: 28.7KΩ to 3.3V (temperature/contact) or 250 Ohms to ground (4-20mA)
A/D Converter Resolution: 12 bits ±2 LSB
Zone Protection: 5.5VDC Metal Oxide Varistor with fast acting diode clamps.
DATA LOGGING
32,000 Samples (all samples include data date and time)
1 second to 1 month sampling rate
User programmable channel selection
Zones 1 – 6
Battery
Input Power
LED INDICATORS
Power On: On steady when the unit is powered on.
Alarm: Off when no alarm exists.
Ethernet Link and Activity LEDs
COMMUNICATION TYPES:
E-Mail – SMTP
Text Messages
8FCQBHFo4VQQPSUFEGPSNBUT)5511%"8"1BOE9.-
SNMP – MIB with Traps, GET, GETNEXT, and SET
MODBUS®/TCP Slave Conformance Class 0 and 1
POWER SUPPLY
1PXFS4VQQMZ7"$7%$)[8XBMMQMVHJOUSBOTGPSNFSXDPSE
Power Consumption: 2 Watts
Power Protection: Metal Oxide Varistor
Battery Backup: Optional 2hr battery backup module (Part #FGD-W610-B).