Setra FLEX Operating Instructions
8
Phone: (800) 257-3872 | Fax: (978) 264-0292 | www.setra.com
1.3 BACnet Networking
FLEX communicates on BACnet networks, an ASHRAE/
ANSI standard building automation protocol. FLEX
supports both BACnet MS/TP and BACnet/IP, allowing
either protocol to be eld-selected for installation.
Connection to the network is then achieved using either
3-wire RS-485 connector or the RJ-45 Ethernet jack on
the rear of the FLEX housing.
FLEX contains approximately 470 BACnet objects with
read/write properties. Nearly all functionality that can be
setorconguredusingtheFLEXtouch-screencan also
be achieved by reading or writing BACnet objects over the
network.Exceptionsincludepasswordchanges,rmware
upgrades, and restore to factory defaults.
For more information on BACnet, refer to Section 4 –
BACnet Integration.
2.0 Rough-in Installation
For FLEX to be installed correctly, the rough-in phase
of the project must be completed properly. This section
will outline the specic considerations the General
Contractormustpayattentionto sothatthe nalwiring
and commissioning will go smoothly.
During rough-in installation there are several options for
installation, depending on whether FLEX was ordered with
on-board or external pressure transducers (or no pressure
sensors at all). Field wiring will be the same, regardless of
pressure sensor presence or location.
2.1 Required Parts to be Supplied by the
Installer
The following is a list of parts required and supplied by the
installer for Setra FLEX RM or FLEX RC:
Triple-gang electrical box (typically called a “masonry”
box) available from most electrical supply houses
Single-deep metal box – used only if FLEX has no on-
board pressure sensor
Garvin TB-325, Madison MSB3G, or equivalent
Double-deep metal box – used with FLEX ordered with
on-board pressure sensor
Garvin TB-335-G, RACO 697, Appleton M3-350, or
equivalent
Power (18 AWG recommended) and signal wire (22 AWG
recommended), as needed.
0.25” (6 mm) O.D. flame retardant polyethylene control
tubing (such as CPChem UL 1820) to run from the
room(s) Pressure Pickup Ports to the FLEX monitor
or external sensors. Maximum 250 feet (76.2 meters)
length.
Pressure tubing T-connectors
EMT conduit (if required by local code)
24 VAC transformer, capacity VA rated for number of
FLEX units powered
250 ohm resistors, if wiring inputs for 4-20 mA current
loops
Door switch SPDT or SPST normally-open, as required
Remote pressure transducers, Setra Model 264 or 267,
as needed
Single-gang electrical box, one per Pressure Pickup Port
2.2 Parts Included with Your Order
The following parts are included with your order:
Setra FLEX main unit
On-boardpressuretransducer(ifon-boardspeciedon
order)
Externalpressuretransducers (if external specied on
order)
Integral FLEX faceplate
Pressure Pickup Ports, quantity specied in original
order
0.25”O.D.nalconnectiontubingwithintegratedsprings
and attached brass barbed couplings, quantity 2
Mounting screws, 6-32 x 1/2 Phillips head, quantity 5
Mating electrical connectors, Phoenix Contact MC plug
kit adapting I/O screw terminals to FLEX unit.

Other manuals for Setra Systems Flex

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Setra Systems Flex and is the answer not in the manual?

Setra Systems Flex Specifications

General IconGeneral
BrandSetra Systems
ModelFlex
CategoryControl Unit
LanguageEnglish