ECShell engineering software
Manual – ECC-DFC field bus controller
Configuring node 192.168.25.20
1. First enter the correct subnetwork into the “Network IP” fields in the main window, plus
the correct node that you would like to connect. In this case, xxx.xxx.xxx.20 is node 1
for this special subnetwork.
2. Call up the Advanced Dialog and select the “Connections” tab.
Note that the relevant node is displayed in the middle and that this field is
deactivated. In addition, the designation “None” is displayed under “Upstream”.
Now instruct this node to accept loads from IP address 192.168.27.25, which is
the next upstream node.
3. Click the button for the IP address, enter the correct value, and click the “Apply”
button.
Note that it takes about 20 seconds for the module to accept the change. The
module is then automatically restarted.
The procedure is now complete, and loads can flow from node 192.168.27.25 to
node 192.168.25.20.