8.7.3 Acknowledging fault messages
The drive may restart automatically depending on the setting after fault elimination or
after a reset. Establish a safe working environment before eliminating a fault if auto-
matic restart of the driven machine is not permitted for safety reasons.
Manual reset
A manual reset can be performed via one of the following options:
• Disconnect the voltage supply. Adhere to a minimum switch-off time of 1 minute.
Switch the supply voltage back on.
• Perform a reset via the power section parameters.
• Perform a reset via the process data interface.
Auto reset
The device has an auto reset function. Due to this function, the software automatically
performs up to 5 resets. You can deactivate the auto reset function temporarily in the
MOVIVISION
®
plant software at the node for the inverter (e.g. for scope recording).
A maximum of 5 auto resets are possible during an auto reset phase. If the auto reset
function has reset 5 errors, no further auto reset is possible. In this case you have to
reset manually.