6
Electrical installation
Installation notes
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
55
6 Electrical installation
6.1 Installation notes
Observe the following points for electrical installation:
Observe the general safety notes.
Comply with all instructions referring to the technical data and the permissible con-
ditions where the device is operated.
The integrated line filter reduces the leakage resistance to less than 500 kΩ.
Therefore, do not include the device in the system test.
6.2 Motor types
The device supports the following motor series from SEW‑EURODRIVE:
DRE..
1)
DRU..
1)
DRS.. DRP..
DRN.. CM..
1) Synchronous gearmotors with LSPM technology DRE..J and DRU..J are not supported.
6.3 Low-voltage supply systems
The device is suited and allowed for operation in the following systems:
TN and TT systems with directly grounded star point
IT systems with non-grounded star point
SEW‑EURODRIVE recommends using insulation monitors with pulse-code mea-
surement. The use of such devices prevents the earth-leakage monitor from mis-
tripping due to the earth capacitance of the inverter.
No EMC limits are specified for interference emission in IT systems.