10
Technical data
Communication and control unit
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
170
10.10 Communication and control unit
10.10.1 Control type
INFORMATION
The overall output power of the 24V voltage supply at the plug connectors for buses
and digital inputs/outputs must not exceed 48W.
Type MNC45A
Engineering Engineering is performed via the Ethernet service interface and the plant
software MOVIVISION
®
.
Binary inputs
Compatibility PLC-compatible according to IEC61131-2:2008-04 type 3 "Standard oper-
ating ranges for digital inputs (current sinking)"
Internal resistance ≈ 4.5 kΩ
Current consumption ≈5.3mA
High level DC+13V–+30V
Low level DC-3V–+5V
Activation delay Typ. 250 μs
Power off delay Typ. 250 μs
Binary outputs
Compatibility PLC-compatible according to IEC61131-2:2008-04 "Rated values and op-
erating ranges (DC) for current-sourcing digital DC outputs"
All outputs are protected against short circuit and overload and external-
voltage-proof up to 30V.
Nominal current Max.DC 500mA per digital output
Output current limit Maximum 1.1A
Inductive loads Dissipation of inductive switch-off energy up to 1J per output at X5001
Freewheeling diodes are not integrated.
Low level DC0V
High level DC24V±10%
Activation delay Typ.100μs
Power off delay Typ.150μs
24 V power supply of the buses
Nominal voltage DC24V±10%
Nominal current Max. DC500 mA per connection
Output current limit Maximum 1.1A
The continuous output current must not exceed 500mA.
26596598/EN – 10/2020