6
Electrical installation
UL-compliant installation
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
56
6.4 UL-compliant installation
INFORMATION
Due to UL requirements, the following chapter is always printed in English indepen-
dent of the language of the documentation.
6.4.1 Power terminals
Use 75 °C copper wire only.
6.4.2 Short circuit current rating
• MOVIPRO
®
is suitable for use on a circuit capable of delivering not more than
200,000 rms symmetrical amperes when protected by fuses and circuit breakers
as described in the tables below.
• MOVIPRO
®
is suitable for use on a circuit capable of delivering not more than
65,000 rms symmetrical amperes when protected by ABB and Rockwell Type E
Combination Motor controllers as described in the tables below.
Max. voltage is limited to 500 V.
6.4.3 Branch circuit protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
For MOVIPRO
®
use branch circuit protection as follows:
Three Phase 380V–500V Voltage Range
SCCR:
200kA/500V
When protected by:
SCCR:
200kA/500V
When protected by:
SCCR: 65kA/480V
When protected
by:
1)
SCCR: 65kA/460V
When protected by:
Model
Non Semicon-
ductor Fuses (cur-
rents are maximum
values)
Inverse-Time Cir-
cuit Breaker
Type E Combinationen Motor Controller
PHC21A-
A022M1-...A-00/..
40A/600V 50A max/500Vmin
ABB, Model
MS132‑6.3
Rated480V, 3HP
Rockwell Automa-
tion, Model
140M‑C2E-B63
Rated460V, 5HP
PHC21A-
A040M1-...A-00/..
40A/600V 50A max/500Vmin
ABB, Model
MS132‑10
Rated480V, 5HP
Rockwell Automa-
tion, Model
140M‑C2E-C10
Rated460V, 7.5HP
PHC21A-
A075M1-...A-00/..
40A/600V 50A max/500Vmin
ABB, Model
MS132‑16
Rated480V, 10HP
Rockwell Automa-
tion, Model
140M‑D8E-C16
Rated460V, 10HP
26596598/EN – 10/2020