6
Electrical installation
UL-compliant installation
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
57
Three Phase 380V–500V Voltage Range
SCCR:
200kA/500V
When protected by:
SCCR:
200kA/500V
When protected by:
SCCR: 65kA/480V
When protected
by:
1)
SCCR: 65kA/460V
When protected by:
Model
Non Semicon-
ductor Fuses (cur-
rents are maximum
values)
Inverse-Time Cir-
cuit Breaker
Type E Combinationen Motor Controller
PHC22A-
A110M1-...A-00/..
40A/600V 50A max/500Vmin
ABB, Model
MS132‑25
Rated480V, 15HP
Rockwell Automa-
tion, Model
140M‑F8E-C25
Rated460V, 20HP
PHC22A-
A150M1-...A-00/..
40A/600V 50A max/500Vmin
ABB, Model
MS132‑32
Rated480V, 20HP
Rockwell Automa-
tion, Model
140M‑F8E-C32
Rated460V, 25HP
1) Drives employing Type E Combination Motor Controller model MS132-16, -25, -32 must be installed with Current Limiter Series
S803W-SCLxxx-SR manufactured by ABB, otherwise SCCR rated 30kA/480Vrms.
For the Connecting Box devices Type PZM use branch circuit protection as follows:
Three Phase 380V–500V Voltage Range
SCCR:
200kA/500V
When protected by:
SCCR:
200kA/500V
When protected by:
SCCR: 65kA/480V
When protected
by:
1)
SCCR: 65kA/460V
When protected by:
Model
Non Semicon-
ductor Fuses (cur-
rents are maximum
values)
Inverse-Time Cir-
cuit Breaker
Type E Combinationen Motor Controller
PZM2XA-A022-
M13-00
60A/600V 50A max/500Vmin – –
PZM2XA-A040-
M14-00
60A/600V 50A max/500Vmin – –
PZM2XA-A075-
M16-00
60A/600V 50A max/500Vmin – –
PZM2XA-A075-
D02-00 – When
installed with
PHC21A-
A022M1-...A-00/..
35A/600V 35A max/500Vmin
ABB, Model
MS132‑6.3
Rated480V, 3HP
Rockwell Automa-
tion, Model
140M‑C2E-B63
Rated460V, 5HP
PZM2XA-A075-
D02-00 – When
installed with
PHC21A-
A040M1-...A-00/..
ABB, Model
MS132‑10
Rated480V, 5HP
Rockwell Automa-
tion, Model
140M‑C2E-C10
Rated460V, 7.5HP
PZM2XA-A075-
D02-00 – When
installed with
PHC21A-
A075M1-...A-00/..
ABB, Model
MS132‑16
Rated480V, 10HP
Rockwell Automa-
tion, Model
140M‑D8E-C16
Rated460V, 10HP
26596598/EN – 10/2020