6
Electrical installation
UL-compliant installation
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
58
Three Phase 380V–500V Voltage Range
SCCR:
200kA/500V
When protected by:
SCCR:
200kA/500V
When protected by:
SCCR: 65kA/480V
When protected
by:
1)
SCCR: 65kA/460V
When protected by:
Model
Non Semicon-
ductor Fuses (cur-
rents are maximum
values)
Inverse-Time Cir-
cuit Breaker
Type E Combinationen Motor Controller
PZM2XA-A150-
D03-00 – When
installed with
PHC22A-
A110M1-...A-00/..
50A/600V 50A max/500Vmin
ABB, Model
MS132‑25
Rated480V, 15HP
Rockwell Automa-
tion, Model
140M‑F8E-C25
Rated460V, 20HP
PZM2XA-A150-
D03-00 – When
installed with
PHC22A-
A150M1-...A-00/..
ABB, Model
MS132‑32
Rated480V, 20HP
Rockwell Automa-
tion, Model
140M‑F8E-C32
Rated460V, 25HP
1) Drives employing Type E Combination Motor Controller model MS132-16, -25, -32 must be installed with Current Limiter Series
S803W-SCLxxx-SR manufactured by ABB, otherwise SCCR rated 30kA/480Vrms.
6.4.4 Motor overload protection
The units are provided with load and speed-sensitive overload protection and thermal
memory retention upon shutdown or power loss. The trip current is adjusted to 150 %
of the rated motor current.
6.4.5 Ambient temperature
The units are suitable for an ambient temperature of 40°C, max. 60°C with derated
output current. To determine the output current rating at temperatures higher than
40°C, the output current should be derated 3% per °C between 40°C and 60°C.
INFORMATION
• Use only tested units with a limited output voltage (V
max
= DC 30V) and limited
output current (I
max
= 8A) as an external DC24V voltage source.
• UL certification does not apply to operation in voltage supply systems with a non-
grounded star point (IT systems).
6.4.6 Wiring diagrams
For wiring diagrams, refer to the MOVIPRO
®
operating instructions, chapter "Electrical
installation".
26596598/EN – 10/2020