EN.
18
1 - 32535 = 1 - 32535 seconds (or milliseconds see Parameter no. 25. Auto OFF timer
enabled for a given amount of seconds (or milliseconds) resolution 100ms
Parameter No. 20 - O (O1) Auto ON with timer
If the load O (O1) is OFF, you can schedule it to turn ON automatically after the period of time
defined in this parameter. The timer resets to zero each time the Device receives an OFF
command, either remotely (from the gateway or associated device) or locally from the switch.
Values size: 2 Byte
Default value: 0
Values & their descriptions:
0 - Auto ON Disabled
1 - 32535 = 1 - 32535 seconds (or milliseconds see Parameter No. 25. Auto ON timer
enabled for a given amount of seconds (or milliseconds) resolution 100ms
Parameter No. 23 - O (O1) contact type - NO/NC
The set value determines the relay contact type for output O (O1) . The relay contact type can be
normally open (NO) or normally closed (NC).
Values size: 1 Byte
Default value: 0
Values & descriptions:
0 - NO
1 - NC
Relay logic:
Par-NO/NC
Command (switch, Z-Wave,..)
Device output state
NO (0)
OFF
OFF (0 V)
NO (0)
ON
ON (230 V)
NC (1)
OFF
ON (230 V)
NC (1)
ON
OFF (0 V)