301
Parameter Description
Parameter Description
Parameter Factory Setting Setting Range Remarks
0 No detection of over torque
155 0% 0~200%
0.1~200%
When detecting the over torque,
alarm is displayed and the motor
stopped.
--- s06~0 s1 651
100%
P.155
output
P.156
OL
Reset
signal
Output current (%)
Invertor display the OL2 alarm,and the output
stopped,the motor stopped too.
(Overload alarm)
full load current level
time
5.42 External Terminal Filter Function (P.157)
P.157 “External terminals filter function selection”
Parameter Factory Setting Setting Range
sm002~0 4 751
P.157 selects response time to the signal of external terminal.
5.43 External Terminal Power Enable Function (P.158)
P.158 “External terminal power enable”
Parameter Factory Setting Setting Range
1~0 0 851
If P.158=1, select the external terminal power enabling function. At this situation, if the
multi-function terminal function is STF, STR, RUN or MPO and the opposite terminal is connected
before the power is on, then the inverter will not run. The user should connect it to the terminal
again and the inverter will start running. If P.158=1, the terminal is connected before the power is
on, and if the power is on, the inverter will run immediately.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SS2-021 Series and is the answer not in the manual?

Shihlin electric SS2-021 Series Specifications

General IconGeneral
BrandShihlin electric
ModelSS2-021 Series
CategoryInverter
LanguageEnglish

Related product manuals