COMMISSIONING  4   
8015078/145N/2019-05 -24 | SICK STEGMANN  OPERATING INSTRUCTIONS  |  AFS60/AFM60 PROFINET 
47
 
Subject to change without notice 
Vendor specific configuration data 
 
Figure 14:  Vendor specific configuration data 
The AFS60/AFM60 PROFINET is supplied with the vendor specific configuration data 
shown. 
4.4.1  Reading the position 
To read from position 2 (the right-justified position value) in the input data for 
telegrams 81 to 84, select STW2_ENC (encoder control word 2) and G1_STW (sensor 1 
control word) (see section 3.4.2 on page 16). 
 
Figure 15:  Reading the  position 
  Set bit 10 of the control word STW2_ENC to 1 (= 0400h, see Table 21 on 
page 23). 
  Set bit 13 of the control word G1_STW to 1 (= 2000h). This results in the cyclic 
output of the position value in G1_XIST2 (see Table 14 on page 20).