osition the brackets near the ends of the housing. For devices with a protective
field height >300mm, the distance between the bracket and the end of the
housing must not exceed 1/4 of the length of the housing. If the device is exposed
to strong vibrations during operation, mount the top bracket at a height where the
offset in the safety light curtain housing rests on the bracket (3).
3
b
T
ightening torque for the screws used to mount the bracket: 5Nmto6Nm.
Tightening torque for the screws used to secure the safety light curtain in the
bracket: 2.5Nmto3Nm (4). Higher torques can damage the bracket, while lower
torques are not secure enough to prevent the safety light curtain from moving.
4
2,5 Nm -
3 Nm
5 Nm -
6 Nm
MOUNTING 5
8021796/1DCM/2022-10-27 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Core Ex II 3GD
33
Subject to change without notice