Technical data
9.1 Motor starters
SIRIUS 3RM1 motor starter
Manual, 11/2013, A5E0345285095020A/RS-AB/002
127
Resistive loads
The tripping characteristic shown does not apply for resistive loads at a setting value of 10 A.
In this case, tripping takes place as follows:
Tripping after
10 A < load current < 15 A 20 s
Load current > 15 A 1 s

Table of Contents