Description
3.5 Functions
SIRIUS 3RM1 motor starter
40 Manual, 11/2013, A5E0345285095020A/RS-AB/002
Actuation time for
starting the test
< 2 s "DEVICE" LED Shows a yellow light
1)
Off
"FAILURE" LED Shows a red light
1)
Off
"STATE" LED Shows a green light
1)
Off
"RESET MODE" button Shows a green light
1)
Off
2 s ... 5 s "DEVICE" LED
• Without load current: Flickering red
• With load current: Flashing red
Off
Motor protection trip test
> 5 s "DEVICE" LED Shows a yellow light Flashing red
"FAILURE" LED Shows a red light Shows a red light
Fault signaling output Active Not active
Switching
elements/motor
Deactivated Unchanged
1)
Exception in the case of 3RM11/3RM13 Failsafe motor starters: in the case of 3RM11/3RM13 Failsafe motor starters,
the LED test is only carried out in the OFF state (without load current). In the ON state (with load current), the LEDs stay
unchanged.
If the 3RM1 motor starter does not respond as in the table above during the function test,
check the connections and the supply to the 3RM1 motor starter. If the fault persists after
correct disconnection, the device must be replaced.