7SR224 Argus Data Comms
©2010 Siemens Protection Devices Limited Chapter 4 Page 41 of 76
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Number
Description
Function
Codes
(dec)
Qualifier
Codes (hex)
Function
Codes (dec)
Qualifier
Codes (hex)
32 6 long floating point Analog Change
Event without Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp
17, 28 (index)
32 7 short floating point Analog Change
Event with Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response
130 (unsol. resp
17, 28 (index)
32 8 long floating point Analog Change
Event with Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response
130 (unsol. resp
17, 28 (index)
50 0 Time and Date
1(read)
07, (limited qty = 1) 129 (response
07 (limited qty = 1)
50 1
(default –
see note 1)
Time and Date
2
(write) 07 (limited qty = 1)
50 3 Time and Date Last Recorded
Time
2 (write) 07 (limited qty)
51 1 Time and Date CTO 129
(response)
130 (unsol.
Resp)
07 (limited
qty = 1)
51 2 Unsychronised Time and Date
CTO
129
(response)
130 (unsol.
Resp)
07 (limited
qty = 1)
52 1 Time Delay Coarse 129
(response)
07 (limited
qty = 1)
52 2 Time Delay Fine 129
(response)
07 (limited
qty = 1)
60 0 Not Defined
60 1 Class 0 Data 1 (read) 06 (no range, or all)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
60 2 Class 1 Data
20 (enbl. unsol.)
21 (dab. unsol.)
22 (assign
class)
06 (no range, or all)
60 3 Class 2 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)