7SR224 Argus Data Comms
©2010 Siemens Protection Devices Limited Chapter 4 Page 42 of 76
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Number
Description
Function
Codes
(dec)
Qualifier
Codes (hex)
Function
Codes (dec)
Qualifier
Codes (hex)
20 (enbl.
unsol.)
21 (dab. unsol.)
22 (assign
class)
06 (no range, or all)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
60 4 Class 3 Data
20 (enbl.
unsol.)
21(dab. unsol.)
22 (assign
class)
06 (no range, or all)
1(read)
00, 01 (start-stop)
129 (response) 00, 01 (start-stop)
80 1 Internal Indications
2
(write)
(see note 3)
00 (start-stop)
index = 7
No Object (function code only) 13 (cold restart)
No Object (function code only) 14 (warm restart)
No Object (function code only) 23 (delay meas.)
No Object (function code only) 24(record current
Note 1: A Default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2,
or 3 scans. Default variations are configurable; however, default settings for the configuration parameters are
indicated in the table above.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with
qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be
responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17 or 28 are always responded.)
Note 3: Writes of Internal Indications are only supported for index 7 (Restart IIN1-7)