7SR224 Argus Data Comms
©2010 Siemens Protection Devices Limited Chapter 4 Page 44 of 76
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Default Static Variation reported when variation 0 requested: 2 (Binary Input with flags)
Default Change Event Variation reported when variation 0 requested: 2 (Binary Input with absolute time)
Point
Index
Name/Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
41 Trip Circuit Fail 2
42 A-Starter 2
43 B-Starter 2
44 C-Starter 2
45 General Starter 2
46 VTS Alarm 2
47 Earth Fault Forward/Line 2
48 Earth Fault Reverse/Busbar 2
49 Start/Pick-up N 2
50 Fault Forward/Line 2
51 Fault Reverse/Busbar 2
52 51-1 2
53 50-1 2
56 51G-1 2
57 50G-1 2
58 51-2 2
59 50-2 2
62 51G-2 2
63 50G-2 2
64 CTS Alarm 2
65 46IT 2
66 46DT 2
67 47-1 2
68 47-2 2
69 46BC 2
70 27/59-1 2
71 27/59-2 2
72 27/59-3 2
73 27/59-4 2
74 59NIT 2
75 59NDT 2
76 81-1 2
77 81-2 2
78 81-3 2
79 81-4 2
80 Auto-reclose active 2
81 CB on by auto reclose 2
82 Reclaim 2
83 Lockout 2
86 51-3 2
87 50-3 2
90 51G-3 2
91 50G-3 2
92 51-4 2
93 50-4 2