7SR224 Argus Data Comms
©2010 Siemens Protection Devices Limited Chapter 4 Page 45 of 76
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Default Static Variation reported when variation 0 requested: 2 (Binary Input with flags)
Default Change Event Variation reported when variation 0 requested: 2 (Binary Input with absolute time)
Point
Index
Name/Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
2
96 51G-4 2
97 50G-4 2
98 Cold Load Active 2
99 E/F Protection Out 2
100 P/F Inst Protection Inhibited 2
101 E/F Inst Protection Inhibited 2
102 SEF Inst Protection Inhibited 2
103 Ext Inst Protection Inhibited 2
105 Battery Test Pass 2
106 Battery Test Fail 2
107 Battery Ohms High 2
108 Battery Volts Low 2
109 Battery Volts High 2
110 Battery Healthy 2
112 Capacitor Ready 2
117 51SEF-1 2
118 50SEF-1 2
119 51SEF-2 2
120 50SEF-2 2
121 51SEF-3 2
122 50SEF-3 2
123 51SEF-4 2
124 50SEF-4 2
125 SEF Out 2
126 Trip Circuit Fail 1 2
127 Trip Circuit Fail 2 2
128 Trip Circuit Fail 3 2
129 CB Total Trip Count 2
130 CB Delta Trip Count 2
131 CB Count To AR Block 2
132 CB Frequent Ops Count 2
133 I^2t CB Wear 2
134 CB-A Reclaim
2
135 CB-A Lockout
2
136 CB-A Total Trip Count
2
137 CB-A Delta Trip Count
2
138 CB-A Count To AR Block
2
139 CB-A I^2t Wear
2
140 CB-A Frequent Ops Count
2
141 CB-A LO Handle Ops Count
2
142 CB-A 79 AR In progress
2
143 PhA Inst Protection Inhibited
2
144 50BF-1 Pole A
2