EasyManua.ls Logo

Siemens 7SR224 - Page 184

Siemens 7SR224
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR224 Argus Data Comms
©2010 Siemens Protection Devices Limited Chapter 4 Page 50 of 76
Binary Output Status Points
Static Object Number: 10
Change Event Object Number: 11
Default Variation reported when variation 0 requested: 2 (Binary Output with flags)
Default Change Event variation 0 requested: 2 (Binary Output absolute time)
Control Relay Output Blocks
Object Number: 12
All objects are default class 2
Point
Index
Name/Description
Supported Control Relay Output Block
Fields
26 Binary Output 26 Pulse On/Latch On
27 Binary Output 27 Pulse On/Latch On
28 Binary Output 28 Pulse On/Latch On
29 Binary Output 29 Pulse On/Latch On
30 Binary Output 30 Pulse On/Latch On
31 Binary Output 31 Pulse On/Latch On
32 Binary Output 32 Pulse On/Latch On
33 LED reset Pulse On/Latch On
34 Settings Group 1 Pulse On/Latch On
35 Settings Group 2 Pulse On/Latch On
36 Settings Group 3 Pulse On/Latch On
37 Settings Group 4 Pulse On/Latch On
38 Settings Group 5 Pulse On/Latch On
39 Settings Group 6 Pulse On/Latch On
40 Settings Group 7 Pulse On/Latch On
41 Settings Group 8 Pulse On/Latch On
42 Auto-reclose on/off Pulse On / Pulse Off / Latch On / Latch Off
43 Hot Line Working on/off Pulse On / Pulse Off / Latch On / Latch Off
44 E/F off/on Pulse On / Pulse Off / Latch On / Latch Off
45 SEF off/on Pulse On / Pulse Off / Latch On / Latch Off
46 Inst Protection off/on Pulse On / Pulse Off / Latch On / Latch Off
47 LOV off/on Pulse On / Pulse Off / Latch On / Latch Off
48 Reset CB Total Trip Count Pulse On/Latch On
49 Reset CB Delta Trip Count Pulse On/Latch On
50 Reset CB Count To AR Block Pulse On/Latch On
51 Reset CB Frequent Ops Count Pulse On/Latch On
52 Reset CB LO Handle Ops Count Pulse On/Latch On
53 Reset I^2t CB Wear Pulse On/Latch On
54 CB 1 Pulse On / Pulse Off / Latch On / Latch Off
55 CB 1 Trip & Reclose Pulse On/Latch On
56 CB 1 Trip & Lockout Pulse On/Latch On
57 Battery Test Pulse On/Latch On
58 Capacitor Test Pulse On/Latch On
59 Demand metering reset Pulse On/Latch On
60 CB-A Pulse On / Pulse Off / Latch On / Latch Off
61 CB-B Pulse On / Pulse Off / Latch On / Latch Off
62 CB-C Pulse On / Pulse Off / Latch On / Latch Off
63 CB-A Trip & Lockout Pulse On/Latch On
64 CB-B Trip & Lockout Pulse On/Latch On
65 CB-C Trip & Lockout Pulse On/Latch On
66 Mode A - 3PTrip3PLO Pulse On/Latch On
67 Mode B - 1PTrip3PLO Pulse On/Latch On
68 Mode C - 1PTrip1PLO Pulse On/Latch On
69 Reset CB-A Total Trip Count Pulse On/Latch On
70 Reset CB-B Total Trip Count Pulse On/Latch On
71 Reset CB-C Total Trip Count Pulse On/Latch On

Table of Contents

Other manuals for Siemens 7SR224

Related product manuals