7SR224 Argus Data Comms
©2010 Siemens Protection Devices Limited Chapter 4 Page 50 of 76
Binary Output Status Points
Static Object Number: 10
Change Event Object Number: 11
Default Variation reported when variation 0 requested: 2 (Binary Output with flags)
Default Change Event variation 0 requested: 2 (Binary Output absolute time)
Control Relay Output Blocks
Object Number: 12
All objects are default class 2
Point
Index
Name/Description
Supported Control Relay Output Block
Fields
26 Binary Output 26 Pulse On/Latch On
27 Binary Output 27 Pulse On/Latch On
28 Binary Output 28 Pulse On/Latch On
29 Binary Output 29 Pulse On/Latch On
30 Binary Output 30 Pulse On/Latch On
31 Binary Output 31 Pulse On/Latch On
32 Binary Output 32 Pulse On/Latch On
33 LED reset Pulse On/Latch On
34 Settings Group 1 Pulse On/Latch On
35 Settings Group 2 Pulse On/Latch On
36 Settings Group 3 Pulse On/Latch On
37 Settings Group 4 Pulse On/Latch On
38 Settings Group 5 Pulse On/Latch On
39 Settings Group 6 Pulse On/Latch On
40 Settings Group 7 Pulse On/Latch On
41 Settings Group 8 Pulse On/Latch On
42 Auto-reclose on/off Pulse On / Pulse Off / Latch On / Latch Off
43 Hot Line Working on/off Pulse On / Pulse Off / Latch On / Latch Off
44 E/F off/on Pulse On / Pulse Off / Latch On / Latch Off
45 SEF off/on Pulse On / Pulse Off / Latch On / Latch Off
46 Inst Protection off/on Pulse On / Pulse Off / Latch On / Latch Off
47 LOV off/on Pulse On / Pulse Off / Latch On / Latch Off
48 Reset CB Total Trip Count Pulse On/Latch On
49 Reset CB Delta Trip Count Pulse On/Latch On
50 Reset CB Count To AR Block Pulse On/Latch On
51 Reset CB Frequent Ops Count Pulse On/Latch On
52 Reset CB LO Handle Ops Count Pulse On/Latch On
53 Reset I^2t CB Wear Pulse On/Latch On
54 CB 1 Pulse On / Pulse Off / Latch On / Latch Off
55 CB 1 Trip & Reclose Pulse On/Latch On
56 CB 1 Trip & Lockout Pulse On/Latch On
57 Battery Test Pulse On/Latch On
58 Capacitor Test Pulse On/Latch On
59 Demand metering reset Pulse On/Latch On
60 CB-A Pulse On / Pulse Off / Latch On / Latch Off
61 CB-B Pulse On / Pulse Off / Latch On / Latch Off
62 CB-C Pulse On / Pulse Off / Latch On / Latch Off
63 CB-A Trip & Lockout Pulse On/Latch On
64 CB-B Trip & Lockout Pulse On/Latch On
65 CB-C Trip & Lockout Pulse On/Latch On
66 Mode A - 3PTrip3PLO Pulse On/Latch On
67 Mode B - 1PTrip3PLO Pulse On/Latch On
68 Mode C - 1PTrip1PLO Pulse On/Latch On
69 Reset CB-A Total Trip Count Pulse On/Latch On
70 Reset CB-B Total Trip Count Pulse On/Latch On
71 Reset CB-C Total Trip Count Pulse On/Latch On