7SR224 Argus Data Comms
©2010 Siemens Protection Devices Limited Chapter 4 Page 51 of 76
Binary Output Status Points
Static Object Number: 10
Change Event Object Number: 11
Default Variation reported when variation 0 requested: 2 (Binary Output with flags)
Default Change Event variation 0 requested: 2 (Binary Output absolute time)
Control Relay Output Blocks
Object Number: 12
All objects are default class 2
Point
Index
Name/Description
Supported Control Relay Output Block
Fields
72 Reset CB-A Delta Trip Count Pulse On/Latch On
73 Reset CB-B Delta Trip Count Pulse On/Latch On
74 Reset CB-C Delta Trip Count Pulse On/Latch On
75 Reset CB-A Count To AR Block Pulse On/Latch On
76 Reset CB-B Count To AR Block Pulse On/Latch On
77 Reset CB-C Count To AR Block Pulse On/Latch On
78 Reset CB-A Frequent Ops Count Pulse On/Latch On
79 Reset CB-B Frequent Ops Count Pulse On/Latch On
80 Reset CB-C Frequent Ops Count Pulse On/Latch On
81 Reset CB-A LO Handle Ops Count Pulse On/Latch On
82 Reset CB-B LO Handle Ops Count Pulse On/Latch On
83 Reset CB-C LO Handle Ops Count Pulse On/Latch On
84 Reset CB-A I^2t Wear Pulse On/Latch On
85 Reset CB-B I^2t Wear Pulse On/Latch On
86 Reset CB-C I^2t Wear Pulse On/Latch On
87 Reset Energy Meters Pulse On/Latch On
88 Remote Mode Pulse On/Latch On
89 Service Mode Pulse On/Latch On
90 Local Mode Pulse On/Latch On
91 Local & Remote Pulse On/Latch On
92 Man Override Sync on/off Pulse On / Pulse Off / Latch On / Latch Off
93 79 Override Sync on/off Pulse On / Pulse Off / Latch On / Latch Off