EasyManua.ls Logo

Siemens 7VK512

Siemens 7VK512
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-ETHOD OF OPERATION6+
6
#
' #

 !UTOMATIC RECLOSURE
 'ENERAL
%XPERIENCE HAS SHOWN THAT APPROXIMATELY  OF
SHORT CIRCUITS ARE CAUSED BY AN ARC ON OVERHEAD
LINES AND SELF
EXTINGUISH AFTER INTERRUPTION BY THE
PROTECTIVE DEVICE 4HE LINE CAN THEREFORE BE RE
EN
ERGIZED 4HIS IS CARRIED OUT BY THE AUTOMATIC RECLO
SURE !2 FUNCTION &IGURE  SHOWS AN EXAMPLE FOR
THE TIME SEQUENCE OF A TWO
SHOT AUTO RECLOSURE
WITH A 2!2 CYCLE FOLLOWED BY A $!2 CYCLE
)F THE CIRCUIT BREAKER POLES CAN BE TRIPPED INDIVIDUAL
LY THEN !2 IS OFTEN CARRIED OUT SINGLE
POLE FOR SING
LE
PHASE FAULTS AND THREE POLE FOR MULTI PHASE
FAULTS IN NETWORKS WITH EARTHED STARPOINT )F THE SHORT
CIRCUIT IS STILL PRESENT AFTER THE AUTO
RECLOSURE ARC
NOT QUENCHED OR METALLIC SHORT CIRCUIT THEN THE PRO
TECTIVE RELAY FINALLY DISCONNECTS THE POWER -ULTIPLE
AUTO
RECLOSURE ATTEMPTS OFTEN WITH A FIRST RAPID
AUTO
RECLOSURE 2!2 AND SUBSEQUENT DELAYED
AUTO
RECLOSE CYCLES $!2 ARE POSSIBLE IN SOME
NETWORKS
6+ ALLOWS AUTOMATIC THREE
POLE SINGLE POLE
SINGLE
AND THREE POLE AS WELL AS SINGLE AND MUL
TI
SHOT RECLOSURE 7ITH MULTI SHOT AUTO RECLOSURE
THE FIRST SHOT IS DESIGNATED WITH 2!2 RAPID AUTO
RE
CLOSURE AND THE SUBSEQUENT SHOTS ARE DESIGNATED
WITH $!2 DELAYED AUTO
RECLOSURE INDEPENDENT ON
THE REAL SETTING OF THE DEAD TIMES OF THE AUTO
RE
CLOSE CYCLES
)N ORDER TO PERFORM SINGLE
POLE OR SINGLE AND
THREE
POLE AUTO RECLOSURE IT IS NECESSARY THAT THE
FEEDER PROTECTION IS ABLE TO ISSUE PHASE SEGREGATED
TRIP COMMANDS
3IGNAL EXCHANGE BETWEEN THE FEEDER PROTECTION AND
THE 6+ AUTO
RECLOSE UNIT MUST BE ACCOM
PLISHED VIA THE BINARY INPUTS AND OUTPUTS OF THE UNIT
&URTHERMORE IT IS ALSO POSSIBLE TO ALLOW THE 6+
TO BE TRIGGERED FROM MORE THAN ONE PROTECTION RELAYS
EG MAIN PROTECTION AND ALTERNATE PROTECTION SEE
3ECTION  )N THIS CASE 6+ CAN PERFORM
THREE
POLE COUPLING FOR BOTH FEEDER PROTECTION RE
LAYS IF ONLY ONE RELAY TRIPS MULTI
POLE OR IF THE PROTEC
TION RELAYS MAKE ATTEMPT TO TRIP SINGLE
POLE IN DIFFER
ENT PHASES
4HE USE OF TWO 6+ RELAYS WITH TWO FEEDER PRO
TECTION RELAYS IS ALSO POSSIBLE AS WELL AS THE USE OF
ONE 6+ WITH A FEEDER PROTECTION AND A SECOND
AUTO
RECLOSE RELAY WITH SEPARATE FEEDER PROTECTION
EXAMPLE SEE 3ECTION 
4HE POSSIBLE PROGRAMS OF THE !2
FUNCTION FOR THE
FIRST !2
CYCLE DESIGNATED IN THE FOLLOWING WITH 2!2
RAPID AUTO RECLOSURE ARE
2!2 02/' 4(2%% 0/,% IE ALL TYPES OF
FAULTS RESULT IN THREE
POLE !2
2!2 02/' 3).',% 0/,% IE SINGLE
PHASE FAULTS RESULT IN SINGLE
POLE !2 MULTI PHASE FAULTS IN
THREE
POLE FINAL DISCONNECTION
2!2 02/' 3).',%4(2%% 0/,E IE
SINGLE
PHASE FAULTS RESULT IN
SINGLE
POLE !2 MULTI PHASE
FAULTS IN THREE
POLE !2
)F MORE THAN ONE RECLOSE ATTEMPT WILL BE CARRIED OUT
THE SECOND AND ANY FURTHER AUTO
RECLOSE CYCLE ARE
DESIGNATED IN THE FOLLOWING WITH $!2 DELAYED
AUTO
RECLOSURE INDEPENDENT ON THE SETTING OF THE
DEAD TIMES OF THE CYCLES )T IS POSSIBLE TO SKIP THE
2!2 CYCLE SO THAT ONLY $!2 CYCLES OCCUR $!2
CYCLES ARE ALWAYS THREE
POLE &OR THE $!2 FUNC
TION THE FOLLOWING PROGRAMS ARE SELECTABLE
$!2 02/' ./ $!2 IE NO $!2 OCCURS UN
SUCCESSFUL 2!2 RESULTS IN FINAL
TRIP
$!2 02/' $!2 7)4(/54 2!2 IE $!2
CYCLES CAN BE CARRIED OUT EVEN
WITHOUT A PRECEDING 2!2 CYCLE
EG 2!2 IS BY
PASSED BE
CAUSE BLOCKED
$!2 02/' $!2 !&4%2 2!2 IE THE $!2
CYCLES CAN ONLY BE INITIATED AFTER
AN UNSUCCESSFUL 2!2
0REREQUISITE FOR INITIATION OF THE !2
FUNCTION IS AL
WAYS THAT THE CIRCUIT BREAKER IS READY FOR OPERATION
WHEN PICK
UP OCCURS 4HIS INFORMATION IS TRANS
MITTED TO THE DEVICE VIA A BINARY INPUT
&URTHERMORE RECLOSURE IS BLOCKED IF THE TRIPPING
COMMAND OCCURS AFTER THE ACTION TIME WHICH CAN BE
SET INDIVIDUALLY FOR 2!2 AND $!2

Table of Contents

Related product manuals