/PERATING INSTRUCTIONS6+
6
#
' #

 3ETTINGS FOR AUTO RECLOSURE ADDRESS BLOCK 
!UTO RECLOSE FUNCTION IS EFFECTIVE ONLY IF CONFIGURED
AS %8)34 UNDER ADDRESS  REFER TO 3ECTION

7ITH THE !2 FUNCTION GENERALLY DISTINCTION IS MADE
BETWEEN THE FIRST !2
CYCLE IDENTIFIED IN THE FOLLOW
ING WITH 2!2 RAPID AUTO
RECLOSURE AND FURTHER
!2
CYCLES WITH MULTI SHOT AUTO RECLOSURE IDENTI
FIED IN THE FOLLOWING WITH $!2 DELAYED AUTO
RECLO
SURE 4HE ABOVE IDENTIFICATIONS ARE REGARDLESS
WHETHER THE DEAD TIMES ARE REALLY
RAPID OR
DELAYED 3ETTING ADDRESSES  TO  ARE COM
MON FOR ALL TYPES OF AUTO
RECLOSURE
7HEN SWITCHING MANUALLY ON A DEAD FAULT IT IS NOR
MALLY DESIRED THAT THE SHORT
CIRCUIT PROTECTION TRIPS
INSTANTANEOUSLY AND THE !2 FUNCTION IS BLOCKED
4HUS ADDRESS  SHOULD REMAIN IN POSITION
-!.#,", 9%3
4HE RECLAIM TIME 4
2%#,!)- ADDRESS  IS THE
TIME PERIOD AFTER WHICH THE NETWORK FAULT IS SUP
POSED TO BE TERMINATED AFTER A SUCCESSFUL
AUTO RE
CLOSE CYCLE ! RENEWED TRIP OF THE FEEDER PROTECTION
WITHIN THIS TIME INCREMENTS THE !2 COUNTER WHEN
MULTI
SHOT !2 IS USED SO THAT THE NEXT !2 CYCLE
STARTS IF NO FURTHER !2 IS ALLOWED THE LAST !2 IS TREATED
AS UNSUCCESSFUL
4HE LOCK
OUT TIME 4",/#+ $9. ADDRESS  IS
THE TIME PERIOD DURING WHICH AFTER AN UNSUCCESSFUL
AUTO RECLOSURE FURTHER RECLOSURES BY 6+ ARE
BLOCKED )F THE MANUAL CLOSE COMMAND IS LED VIA THE
6+ THEN THIS WILL BE BLOCKED ALSO 4HIS TIME MUST
BE LONGER THAN THE RENEWED READINESS FOR OPERATION
OF THE CIRCUIT BREAKER UNLESS THE #" IS SUPERVISED IN
THE RELAY SEE BELOW ADDRESS  )F THIS TIME IS SET
TO 0 BREAKER CLOSE COMMANDS ARE LOCKED )N THIS
CASE SWITCHING CAN BE UNLOCKED ONLY WHEN THE
BINARY INPUT
!2 2ESET &.O  IS ENERGIZED )T
MUST BE ENSURED IN THIS CASE THAT THIS FUNCTION IS AL
LOCATED TO A BINARY INPUT
4HE SET TIME FOR 4",/#+
-# ADDRESS  MUST
COVER THE TIME FOR SAFE CLOSING AND OPENING OF THE CIR
CUIT BREAKER  S TO S )F THE FEEDER PROTECTION DE
TECTS A FAULT WITHIN THIS TIME THREE
POLE FINAL TRIP
COMMAND IS ISSUED AND RECLOSURE IS BLOCKED PRO
VIDED -!.#,", ADDRESS  SEE ABOVE IS
SWITCHED /.
4HE DURATION OF THE CLOSING COMMAND HAS ALREADY
BEEN SET WHEN SETTING THE GENERAL PARAMETERS AD
DRESS  3ECTION 
! PREREQUISITE FOR INITIATION OF THE !2 FUNCTION IS THAT
THE CIRCUIT BREAKER IS READY FOR AT LEAST ONE TRIP
CLOSE
CYCLE WHEN THE FEEDER PROTECTION TRIPS 4HIS INFORMA
TION HAS TO BE GIVEN TO THE RELAY VIA THE BINARY INPUT
#" READY &.O  )N CASE SUCH INFORMATION IS
NOT AVAILABLE FROM THE #" CIRCUIT INTERROGATION OF
#" READY CAN BE SUPPRESSED BY SETTING THE PA
RAMETER #" 42)0 ./ IE #" INTERROGATION FOR
ST TRIP OTHERWISE RECLOSURE WOULD NOT BE POSSIBLE
AT ALL
!DDITIONALLY IT IS POSSIBLE TO INTERROGATE READINESS OF
THE CIRCUIT BREAKER BEFORE EACH FURTHER RECLOSE COM
MAND OR BEFORE EVERY OTHER RECLOSE COMMAND 3ET
TING IS MADE IN ADDRESS 
#" #,/3% #" 7)4( %!#( !2 INTERROGATION IS
MADE BEFORE EACH RECLOSE COM
MAND
#" #,/3% #" .%6%2 INTERROGATION IS NOT
MADE OR ONLY AT THE MOMENT OF THE
FIRST TRIP COMMAND AS PARAMETERIZED
UNDER ADDRESS 
#" #,/3% #" 7)4( ND !2 INTERROGATION IS
MADE BEFORE EVERY OTHER RECLOSE
COMMAND IE BEFORE THE ND TH
ETC EVERY TRIP
CLOSE CYCLE IS VALID
REGARDLESS WHETHER IT IS 2!2 OR $!2
)N ORDER TO MONITOR THE REGENERATION TIME OF THE CIR
CUIT BREAKER A SPECIAL CIRCUIT BREAKER SUPERVISION
TIME 4
#" 3506 CAN BE SET UNDER ADDRESS 
4HIS TIME SHOULD BE SET SLIGHTLY HIGHER THAN THE RE
GENERATION TIME OF THE BREAKER AFTER A TRIP
CLOSE
CYCLE )F THE CIRCUIT BREAKER IS NOT YET READY AFTER THIS
TIME RECLOSURE IS SUPPRESSED
&INALLY ADDRESS  DETERMINES FOR WHICH RECLOSE
CYCLES SYNCHRONISM OR VOLTAGE SHALL BE CHECKED BY
THE SYNCHRO
CHECK FUNCTION IF FITTED AND USED )N
THE CASES WHICH ARE SET THERE RECLOSURE IS BLOCKED
AS LONG AS THE CONDITIONS AS SET FOR THE SYNCHRO
CHECK FUNCTION ARE NOT FULFILLED