861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11 93/214
Installation
Installing disconnectable busbar components
When disconnectable busbar components such as voltage transformers with fuses must be
mounted, the kinematic system has to be assembled first.
Assembling the
kinematic system
The operating shaft with coupling rods ① at the upper row of busbar housings and the
operating shaft ② at the lower row of busbar housings have been pre-assembled at the
factory.
Interconnect the upper operating shaft ② and the lower operating shaft ④ by means of a
double coupling rod ③ .
Fig. 103: Operating shafts at the busbar housings
Operating shaft with coupling rod for
upper row of busbar housings
Operating shaft for lower row of
busbar housings
Fig. 104: Fixing of operating shafts ,
at the busbar housing
Bearing plate for fixing the operating shaft at the busbar housing
Operating shaft for upper busbar housing
Double coupling rod, interconnects upper and lower operating shaft
Operating shaft for lower busbar housing
Busbar housing (lower row)
Earthing lug
Busbar housing (upper row)