Emergency mode
Emergency mode can be maintained in the event the heat pump is not working
properly.
w Navigation to special operation menu is described in Section "Operate special
functions [➙ 66]".
1. Select "Emergency mode" = "On".
The function is activated.
2. Conclude the function with "Emergency mode" = "Off".
Drain refrigerant
You manually initiate the draining of refrigerant with this special function.
w Navigation to special operation menu is described in Section "Operate special
functions [➙ 66]".
1. Select "Drain refrigerant" = "On".
The function is activated.
2. Conclude the function with "Drain refrigerant" = "Off".
Initiate defrost
The manual defrost function is used for the evaporator of an air/water heat pump.
Additional information on the defrost function is available in the user's guides for
your controller.
w Navigation to special operation menu is described in Section "Operate special
functions [➙ 66]".
l Select "Initiate defrost" = "Yes".