$SSHQGL[
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
12-22 A5E00105492-03
 5XOHVIRUWKH7UDQVLWLRQ3RLQWVEHWZHHQ/LJKWQLQJ3URWHFWLRQ
=RQHV!DQG+LJKHU
5XOHVIRUWUDQVLWLRQSRLQWV!DQGKLJKHUORFDOHTXLSRWHQWLDOERQGLQJ
The following measures must be taken on all transition points 1 <-> 2 and higher:
Set up local equipotential bonding at each subsequent lightning protection zone
transition.
Include all lines (also metal conduits, for example) in the local equipotential
bonding of all subsequent lightning protection zone transition points.
Include all metal installations located within the lightning protection zone in the
local equipotential bonding (for example, metal part within lightning protection
zone 2 at transition 1 <-> 2).
$GGLWLRQDO0HDVXUHV
We recommend fine-wire fusing for following elements:
All 1 <-> 2 and greater lightning protection zone transitions
All cables that run within a lightning protection zone and are longer than 100 m
/LJKWQLQJSURWHFWLRQHOHPHQWIRUWKH9'&SRZHUVXSSO\PRGXOH
Always use the Blitzductor VT, type AD 24 V SIMATIC for the 24 VDC power
supply module of the S7-300. All other surge protection components do not meet
the required tolerance range of 20.4 V to 28.8 V of the S7-300 power supply.
/LJKWQLQJ&RQGXFWRUIRU6LJQDO0RGXOHV
You can use standard surge protection components for the digital I/O modules.
However, please note that these only permit a maximum of 26.8 V for a rated
voltage of 24 VDC. If the tolerance of your 24 VDC power supply is higher, use
surge protection components with 30 VDC rating.
You can also use Blitzductor VT, type AD 24 V. Note that input current can
increase if negative input voltages are generated.

Table of Contents

Other manuals for Siemens CPU 315-2 DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 315-2 DP and is the answer not in the manual?

Siemens CPU 315-2 DP Specifications

General IconGeneral
Memory64 KB
Power Supply24 V DC
Order Number6ES7 315-2AG10-0AB0
Number of DP Masters1
Number of DP Slaves124
Load Memory64 KB
Number of Timers256
Number of Counters256
Data Memory64 KB
Operating Temperature0 to 60 °C
Integrated InterfacesMPI, DP
Digital OutputsNot integrated
Analog InputsNot integrated
Analog OutputsNot integrated
Programming LanguagesLAD, FBD, STL
Digital InputsNot integrated
Weight660 g