&RQILJXULQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
5-7
 $UUDQJLQJ0RGXOHVRQD6LQJOH5DFN
$UH\RXXVLQJRQHRUPRUHUDFNV"
The number of racks you need will depend on your application.
5HDVRQVIRUXVLQJDVLQJOHUDFN
Compact, space-saving use of all your modules
Centralized use of your modules
Fewer signals to be processed
5HDVRQVIRUGLVWULEXWLQJPRGXOHVEHWZHHQVHYHUDOUDFNV
More signals to be processed
Insufficient slots available
7LS:
If you opt for installation on a single rack, insert a dummy module to the right of the
CPU (order no.: 6ES7 370-0AA01-0AA0). This gives you the option of inserting a
second rack for your application in the future, simply by replacing the dummy
module with an interface module and without having to reinstall and rewire the first
rack.
5XOHV$UUDQJLQJPRGXOHVRQDVLQJOHUDFN
The following rules apply to single-rack module installations:
No more than eight modules (SM, FM, CP) may be installed to the right of the
CPU.
All modules mounted on a rack must not consume more than a total of 1.2 A
from the S7-300 backplane bus.
7KHSRZHUFRQVXPSWLRQRIPRGXOHV
is listed under the technical data, e.g. 60RGXOH'DWD5HIHUHQFH0DQXDOor in
the 5HIHUHQFH0DQXDOfor your CPU

Table of Contents

Other manuals for Siemens CPU 315-2 DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 315-2 DP and is the answer not in the manual?

Siemens CPU 315-2 DP Specifications

General IconGeneral
Memory64 KB
Power Supply24 V DC
Order Number6ES7 315-2AG10-0AB0
Number of DP Masters1
Number of DP Slaves124
Load Memory64 KB
Number of Timers256
Number of Counters256
Data Memory64 KB
Operating Temperature0 to 60 °C
Integrated InterfacesMPI, DP
Digital OutputsNot integrated
Analog InputsNot integrated
Analog OutputsNot integrated
Programming LanguagesLAD, FBD, STL
Digital InputsNot integrated
Weight660 g

Related product manuals