Periphery board (250p) FCI2016
Technical data
1
21 |
46
Building Technologies
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016
-
02
-
1.12 Technical data
Supply input Plug strip X301/302
Operating voltage DC 24 V nominal, filtered
Operating current (standby) 120 mA
Max. operating current. 136 mA
Input current (active)
Design
PS170W (only fire detection systems) 6.5 A at
1 x PS300W 11.5 A
2 x PS300W 20 A
Not power limited
Battery output Plug strip X303
Voltage
DC 20.4 V…DC 26.4 V
(DC 24 V nominal)
Curent Max. 11.5 A
NAC circuit Plug strip X601
Voltage DC 24 V
Special Application for strobe loads
Regulated for non-pulsing loads
Standby operating current Max. 10 mA
Active operating current Max. 1x class A circuit or 2x class B circuits
Max. 3 A for 1x class A circuit
Max. 3 A per class B circuit
2x 3 A = 6 A for 2x class B circuits
Max. circuit resistance 1.4 Ω @ 3.0 A
Supervised for Open circuit
Short circuit
Ground fault
Design Short-circuit protection
Voltage surge protection
Power limited
AUX output Plug strip X1001
Voltage DC 24 V nominal "Special Application"
For use with: FN2006/FN2007, HZM, HCP,
FCA2018, FT2014/FT2015, FTI2001
Curent Max. 1.5 A
Design Short-circuit protection
Voltage surge protection
Power limited