Periphery board (250p) FCI2016
Technical data
1
23 |
46
Building Technologies
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016
-
02
-
Connection terminals
Inputs, outputs and detector
circuits
Design Plug-in screw terminals
Admissible cable cross-
section
Once 12...18 AWG or twice 16...18 AWG
Voice alarm supply Connecting plug X304
Output +24 V
Output voltage DC 24 V nominal, filtered
Max. output current 20 A
Design Not power limited
Short-circuit-proof