Periphery board (500p) FCI2017
2
43 |
Building Technologies
Bell follower input Plug strip X1001
Voltage DC 24 V filtered or full wave
Curent Max. 4 mA
Design Voltage surge protection
Detector circuits Terminal strips X1401 circuit card 1, circuit 1
X1402 circuit card 1, circuit 2
X1801 circuit card 2, circuit 3
X1802 circuit card 2, circuit 4
Output voltage DC 24 V, filtered
Number of integrated circuit cards 2
Output current per integrated circuit card Max. 500 mA
Addressable devices per integrated circuit
card
Max. 252
Connectable circuits per integrated circuit
card
2 style 6 or 4 style 4 (mixed variants are
possible)
Protocol FDnet/C-NET
Circuit resistance Max. 180 Ω
Capacity 500 nF per circuit
Cable types All (twisted recommended)
You will find detailed specifications in the
following documents:
● A6V10315013 for Desigo
● A6V10333396 for Cerberus PRO
Connectable devices See List of compatibility
Monitored for ● Ground fault
● Short circuit
● Open circuit
● Circuit capacitance
Design ● Short-circuit-proof
● Voltage surge protection
● Open circuit
● Power limited
Relay contacts Plug strip X1201
Design ● Relay output
● Break or make contact
● Nonpower limited
● Alarm and trouble active in degraded
mode operation
Switching voltage DC 30 V or AC 120/240 V ohmic
Switching current
5 A @ DC 30 V or AC 120 V
4 A @ AC 240 V