BASIC OPERATION
PMI OPERATION MANUAL | CHAPTER 1
1-10
Security When a security is detected, the yellow Security LED blinks, the System’s internal
audible pulses, and the event(s) display on the screen with a blinking exclamation
mark (!). This event listing displays the Event Custom Message, the Time of the event
occurrence and the Security Event Category (i.e., Door, Monitor Point, etc.).
In addition, the System responds to securities with other output functions (as
programmed in the Zeus tool).
An Acknowledge Security soft key displays in the bottom left corner of the screen.
Press this key to acknowledge each security and to silence the local audible. The
blinking exclamation point (!) then changes to a check mark (). See Figure 1-6.
Trouble When a trouble is detected, the yellow Trouble LED blinks, the System’s internal
audible pulses, and the event(s) display on the screen with a blinking exclamation
mark (!). This event listing displays the Event Custom Message, the Time of the event
occurrence and the Trouble Event Category (refer to the Trouble Event: Category
Cross Reference Table that follows).
ECNEREFER-SSORCYROGETAC:TNEVEELBUORT
yrogetaCeciveDlacisyhP
ECIVED ,11-TPFH,11-PFH:troperelbuorttiucric/enozroecivedtupnidesivrepusynA
.stiucricdesivrepusyllaudividni61-MIS,MCO,SMH,secivedIRTH
ENOZsenozMZH,senozMAZ,senozCAZ,senozCIZ
ELUDOM .CIN,XSP,CSP,MAZ,CIZ,CLD,IMP,.e.i-elbuorteludomdesivrepusynA
METSYS cificepsaotdetniopniptoneratahtseruliaf/elbuortdetaler-metsySynA
.ecivedroenoz,eludom
KROWTENTENH
.elbatcelesdleiftoneradnayrotcafehtybdenifed-erperaseirogetacesehtfollA:ETON
In addition, the System responds to troubles with other output functions (as pro-
grammed in the Zeus tool).
An Acknowledge Trouble soft key displays in the bottom left corner of the screen.
Press this key to acknowledge each trouble and to silence the local audible. The
blinking exclamation point (!) then changes to a check mark (). See Figure 1-6.
24 Hour Trouble Resound If acknowledged troubles remain in the queue,
the system will sound the local audible every 24
hours as a reminder. A 24 Hour Trouble Resound
pop-up box (See Figure 1-10) will appear on the
PMI and the sounder will remain on until it is
silenced. To silence the local audible, touch any
PMI key or press the Silence button on the
touch screen.
24 Hour Trouble
Resound
Silence
Figure 1-10
24 Hour Trouble Resound Pop-up Box
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Other manuals for Siemens FIREFINDER-XLS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FIREFINDER-XLS and is the answer not in the manual?

Siemens FIREFINDER-XLS Specifications

General IconGeneral
BrandSiemens
ModelFIREFINDER-XLS
CategoryControl Panel
LanguageEnglish

Related product manuals