Web-based configuration
5.4 Web pages
LOGO! CIM
Operating Manual, 10/2021, A5E51250518-AA
63
Set data transfer table
For the connections that CIM works as master, you need to set the following values in the
data transfer table:
1. Click to add a new row.
2. Click to choose the UDM address type of CIM.
3. Input one address in the UDM start address field of CIM .
4. Click to choose data transfer directions.
5. Click to choose the Modbus address type of the remote Modbus RTU slave.
6. Input the Modbus start address of the remote Modbus RTU slave .
7. Input the length of the data need to be transferred .
8. Input the Unit ID of the remote Modbus RTU slave (Slave ID/Address) .
9. To set the time interval that CIM synchronizes the data with the server, select the check box
and input the specified time interval .
The default minimum transmit interval is 80 milli-second.
10.Save your changes and close the data transfer table.