7ML19981FB05 MultiRanger 100/200 – INSTRUCTION MANUAL Page 147
mmmmm
Parameters
MultiRanger 200
P202 mA Output Allocation
Sets the input source from which the mA output is calculated.
Please note that parameter P202 values vary between the MultiRanger 100 and the
MultiRanger 200.
MultiRanger 100
MultiRanger 200
Primary Index mA output
Values
value mA function Operation (P001)
0OFF
1 level level, differential, or average
2space space
3 distance distance
4 volume level or space
5flow OCM
6head
7 volume rate
8mA input
9 comms input
Related
P202 mA Output Allocation
•P911 mA Output Value
Altered By •P001 Operation
Primary Index mA output
Values
1* Point 1
2 Point 2
Related P201 mA Output Function
Primary Index mA output
Values
1* Point 1
2 Point 2
3 Point 3
Related P201 mA Output Function