Page 146 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB05
mmmmm
Parameters
mA Output (P200 to P219)
P200 mA Output Range
Determines the mA output range.
If either 1 or 2 is selected, the mA output is directly proportional to the mA Function. If
either 3 or 4 is selected, then the output is inversely proportional.
P201 mA Output Function
Alters the mA output/measurement relationship.
Please note that parameter P201 values vary between the MultiRanger 100 and the
MultiRanger 200.
MultiRanger 100
Primary Index mA output
Values
0off
1 0 to 20 mA
2* 4 to 20 mA
3 20 to 0 mA
4 20 to 4 mA
Related P911 mA Output Value
Primary Index mA output
Values
value mA function Operation (P001)
0OFF
1level level
2space space
3 distance distance
Related
P202 mA Output Allocation
•P911 mA Output Value
Altered By •P001 Operation