14
2. Technical data
SITRANS F M
MAG 3100, MAG 3100 HT and MAG 3100 P
Type MAG 3100 MAG 3100 HT (High Temperature) MAG 3100 P
Operating pressure
Operating pressure
Neoprene 0.01 ... 100 bar PTFE Teflon PTFE Teflon
[abs. bar] (maximum (0.15 ... 1450 psi) - DN 15 ... 300 (½" … 12") - DN 15 ... 300 (½" … 12") :
operating pressure EPDM 0.01 ... 40 bar (0.15 ... 580 psi) (130/180 °C (266/356°F)): 0.3 ... 40 bar (4 ... 580 psi)
decreases with Linatex
®
0.01 ... 40 bar 0.6 ... 50 bar (9 ... 725 psi) PFA
increasing operating (0.15 ... 580 psi) (180 °C (356 °F) - DN 25 ... 100 (1" … 4"):
temperature and with • Ebonite 0.01 ... 100 bar PTFE has factory-mounted grounding 0.01 ... 50 bar (0.15 ... 725 psi)
stainless steel flanges) (0.15 ... 1450 psi) SS rings type E & SS terminal box)
• PTFE PFA
DN 300 (≤ 12"): - DN 25 ... 100 (1" … 4"):
0.3 ... 50 bar (4 ... 725 psi)
0.01 ... 50 bar (0.15 ... 725 psi)
350 DN 600
(14“ DN 24"):
0.3 ... 40 bar (4 ... 580 psi)
PFA
- DN 25 ... 100 (1" … 4"):
0.01 ... 50 bar (0.15 ... 725 psi)
Enclosure rating IP67/NEMA 4X/6 to EN 60529, 1 m H
2
O for 30 min
Option: IP68/NEMA 6P to EN 60529, 10 mH
2
O cont. (no ATEX)
Pressure drop at 3 m/s As straigth pipe
Test pressure 1.5 x PN (where applicable)
Mechanical load 18 ... 1000 Hz random in x, y, z, directions for 2 hours according to EN 60068-2-36
Sensor: 3.17 grms
Sensor with compact MAG 5000/6000 mounted transmitter: 3.17 grms
Temperature of medium Neoprene 0 … +70 °C (32 … 158 °F) PTFE -20 … +130 °C (-4 … +266 °F) • PTFE -20 … +130 °C (-4 … +266 °F)
EPDM -10 … +70 °C (14 … 158 °F) PTFE -20 … +180 °C (-4 ... +356 °F) • PFA -20 … +150 °C (-4 … +300 °F)
Linatex
®
(rubber) -40 … +70 °C Factory-mounted grounding rings
(-40 … +158 °F) (for temperatures type E and SS terminal box. Can only
below -20 °C (-4 °F) AISI 304 or 316 be used with remote transmitter.
flanges must be used) PFA -20 … +150 °C (-4 … +300 °F)
Ebonite 0 … 95 °C (32 … 203 °F)
PTFE -20 … +100 °C (-4 … +212 °F)
PFA -20 … +100 °C (-4 … +212°F)
EMC 89/336 ECC
Design
Weight See dimensional drawings
Flange and housing Carbon steel ASTM A 105, with material corrosion-resistant two-component epoxycoating (min. 150 μm)
or
AISI 304 (1.4301) flanges and carbon steel housing, with corrosion-resistant two-component epoxy coating (min. 150 μm)
or
AISI 316 L (1.4404) flanges and housing, polished
Measuring pipe material AISI 304 (1.4301)
2.3 Sensor MAG 3100, MAG 3100 HT and MAG 3100 P (continued)

Table of Contents