Page 206 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB05
mmmmm
Parameters
P823 Reform Echo
Smoothes jagged peaks in the echo profile.
Use this feature, when monitoring solids (P002 = 2), if the reported level fluctuates
slightly, though the monitored surface is still. Enter the amount (in ms) of long shot Echo
Profile smoothing required. When a value is keyed in, the nearest acceptable value is
entered.
P825 Echo Marker Trigger
The point on the primary echo on which the measured value is based.
Use this feature if the reported material level fluctuates slightly, due to a variable rise in
the leading edge of the true echo on the Echo Profile.
Enter the value (in percent of echo height) to ensure the Echo Lock Window intersects the
Echo Profile at the sharpest rising portion of the Echo Profile representing the true echo.
This value is preset to 50%.
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values
0 = OFF (preset)
greater = wider
Related
P002 Material
P820 Algorithm
P821 Spike Filter
P822 Narrow Echo Filter
P825 Echo Marker Trigger
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values
Range: 5 to 95%
Preset: 50%
Related
P820 Algorithm
P821 Spike Filter
P822 Narrow Echo Filter
P823 Reform Echo