Parameter Description
responseTimeout
You can set the timeout interval used to wait for a response from the
Modbus device. If the waiting before receiving the response is longer than
the given timeout, an error will be generated. Range: 500ms (default)
60000ms
responseSuspensionTime
If a byte timeout or a response timeout was detected, then this waiting
time is added before the next request is started. During this time any
response from the Modbus device will be flushed. Range: 0ms 45000ms.
(default: 1000ms)
requestDelay
You can set the time between the response from the Modbus device and
the next request to this Modbus device. Range: 0ms (default) 10000ms
Modbus TCP data point parameter
In order to collect the data of your Modbus TCP device, you must add new data points.
The following picture shows the data point parameter window:
The following table shows the parameter of the Modbus TCP data point window:
Parameter Description
Data Type Data type supported by backend (e.g. INT).
Configuring protocols
4.4 Overview of Modbus TCP protocol for MindConnect Nano
MindConnect Nano
System Manual 7/2023 60

Table of Contents

Other manuals for Siemens MindConnect Nano

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MindConnect Nano and is the answer not in the manual?

Siemens MindConnect Nano Specifications

General IconGeneral
BrandSiemens
ModelMindConnect Nano
CategoryGateway
LanguageEnglish

Related product manuals