System Messages
C-4
MP270 Equipment Manual
Release 01/99
RemedyEffect/CauseNumber
60011 An attempt was made to copy a file to itself.
It is possible that the Windows NT user has no access
rights to one of the two file.
Check the path of the
source-/target file.
Using Windows NT with NTFS:
The user executing ProTool/Pro RT
must be granted access rights for
the files.
70010 The application could not be started because it could
not be found in the path specified or insufficient
memory space was available.
Check whether the application
exists in the specified path or close
other applications.
70011 The system time could not be modified This may be
due to the following:
– an impermissible time was transferred in the PLC
job,
– the Windows NT user has no user rights to modify
the system time.
Check the time which is to be set.
Under Windows NT: The user
executing ProTool/Pro RT must be
assigned the rights to modify the
system time from Windows NT
(administration/user manager,
guidelines).
70012 An error occurred when executing the function “Exit
Runtime” with the option “Exit also Windows”.
Windows and ProTool/Pro RT are not terminated.
A possible cause is that other applications cannot be
terminated.
Terminate all applications currently
running.
Then terminate Windows.
70013 The system time could not be modified because an
invalid value was entered. Incorrect separators may
have been used.
Check the time which is to be set.
70014 The system time could not be modified This may be
due to the following:
– an impermissible time was transferred
– the Windows NT user has no user rights to modify
the system time,
– Windows rejects the setting request.
Check the time which is to be set.
Under Windows NT: The user
executing ProTool/Pro RT must be
assigned the rights to modify the
system time from Windows NT
(administration/user manager,
guidelines).
70015 The system time could not be read because Windows
rejects the reading function.
–
70016 An attempt was made to select a screen by means of
a function or job. This is not possible because the
screen number specified does not exist.
Or: a screen could not be generated due to
insufficient system memory.
Check the screen number in the
function or job with the screen
numbers configured.
Refer the number to a screen, if
necessary.
80001 – Store the file or table by executing
a ‘move’ or ‘copy’ function.
80002 A line is missing in the specified archive. –
80003 The copying process for archiving was not successful.
In this case, it is advisable to check any subsequent
system messages, too.
–
80005 The copying process for archiving was not successful.
If an automatic trigger is used for archiving, data may
have been lost.
–