System Messages
C-5
MP270 Equipment Manual
Release 01/99
RemedyEffect/CauseNumber
80006 Since archiving is not possible, this causes a
permanent loss of the functionality.
In the case of databases, check
whether the corresponding data
source exists and start up the
system again.
80008 Since archiving is not possible, this causes a
permanent loss of the functionality.
Restart the system when the full
functionality is required.
80010 Since the path was incorrectly entered in ProTool, this
causes a permanent loss of the functionality.
Configure the path for the
respective archive again and
restart the system when the full
functionality is required.
80011 Target archives are open. You have two minutes in which to
close the target archive, then a
new attempt is made.
80012 Archive values are stored in a buffer. If the values are
read to the buffer faster than they can be physically
written (e.g. using a hard disk), overloading may occur
and recording is then stopped.
Archive less values.
Or increase the recording interval.
80013 The overload status no longer applies. Archiving
resumes the recording of all values.
80014 The same action was triggered twice in quick
succession. Since the process is already in operation,
the action is only carried out once.
110000 The operating mode status has been changed. The
operating mode is now offline.
110001 The operating mode status has been changed. The
operating mode is now online.
110002 The operating mode status has not been changed. Check the connection to the PLCs.
Check whether the address area
for the area pointer “Coordination”
in the PLC is available.
120000 The trend is not displayed because an incorrect axis
to the trend, or incorrect trend, has been configured.
Change the configuration.
120001 The trend is not displayed because an incorrect axis
to the trend, or incorrect trend, has been configured.
Change the configuration.
120002 The trend is not displayed because the tag assigned
tries to access an invalid PLC address.
Check whether the data area for
the tag exists in the PLC, the
configured address is correct or
the value range for the tag is
correct.
130000 The action was not executed. Close other applications.
Delete files no longer required from
the hard disk.
130001 The action was not executed. Delete files no longer required from
the hard disk.
130002 The action was not executed. Close other applications.
Delete files no longer required from
the hard disk.