System Messages
C-6
MP270 Equipment Manual
Release 01/99
RemedyEffect/CauseNumber
140000 Online connection to the PLC has been successfully
established.
–
140001 Online connection to the PLC has been disconnected. –
140003 No tag updating or writing is executed. Check the connection and whether
the PLC is switched on.
Check the parameter definitions in
the Control Panel using “Set
PU/PC interface”.
Restart the system.
140004 No tag updating or writing is executed because the
access point or the subrack configuration is incorrect.
Check the connection and whether
the PLC is switched on.
Check the access point or the
subrack configuration (MPI, PPI,
PROFIBUS) in the Control Panel
with “Set PG/PC interface”.
Restart the system.
140005 No tag updating or writing is executed because the
address of the operating unit is incorrect (possibly too
high).
Use a different operating unit
address.
Check the connection and whether
the PLC is switched on.
Check the parameter definitions in
the Control Panel using “Set
PU/PC interface”.
Restart the system.
140006 No tag updating or writing is executed because the
baud rate is incorrect.
Select a different baud rate in
ProTool/Pro (according to subrack,
profile, communication peer, etc.).
140007 No tag updating or writing is executed because the
bus profile is incorrect (see %1).
The following parameters could not be entered in the
registry:
1: Tslot
2: Tqui
3: Tset
4: MinTsdr
5: MaxTsdr
6: Trdy
7: Tid1
8: Tid2
9: Gap Factor
10: Retry Limit
Check the user defined bus profile.
Check the connection and whether
the PLC is switched on.
Check the parameter definitions in
the Control Panel using “Set
PU/PC interface”.
Restart the system.