System Messages
C-7
MP270 Equipment Manual
Release 01/99
RemedyEffect/CauseNumber
140008 No tag updating or writing is executed because the
configuration data is incorrect:
The following parameters could not be entered in the
registry:
0: General errors
1: Incorrect version
2: Profile cannot be entered in the registry.
3: Sub-network type cannot be entered in the
registry.
4: Target rotation time cannot be entered in the
registry.
5: Highest addresse (HSA) incorrect.
Check the connection and whether
the PLC is switched on.
Check the parameter definitions in
the Control Panel using “Set
PU/PC interface”.
Restart the system.
140009 No tag updating or writing is executed because the
module for the S7 communication was not found.
Re-install the module in the Control
Panel using “Set PG/PC interface”.
140010 No S7 communication peer could be found because
the PLC is switched off.
DP/T: The option “Is not active as the only master” is
set in the Control Panel under “Set PG/PC interface”.
Switch the PLC on.
DP/T:
If only one master is connected to
the network, deactivate the option
“Is not active as the only master” in
“Set PG/PC interface”.
If the network has more than one
master, switch this master on. Do
not modify any settings here,
otherwise a bus fault may occur.
140011 No tag updating or writing is executed because
communication is interrupted.
Check the connection and that the
communication peer is switched
on.
140012 There is an initialization problem (e.g. when
ProTool/Pro RT has been terminated in the Task
Manager).
Or: another application (e.g. STEP7, WINCC) is active
with different bus parameters and the driver cannot be
started with the new bus parameters (e.g. baud rate).
Restart the operating unit.
Or start ProTool/Pro RT first and
then the other applications.
140013 The MPI cable is not plugged in and, thus, there is no
power supply.
Check the connections.
140014 In the configuration modify the
operating unit address.
140015 Incorrect baud rate
Or: incorrect bus parameter (e.g. HSA)
Or: OP
address > HSA
Or: incorrect interrupt vector (interrupt does not arrive
at the driver)
Correct the incorrect parameters.
140016 Change the interrupt number.
140017 Change the interrupt number.