System Messages
C-8
MP270 Equipment Manual
Release 01/99
RemedyEffect/CauseNumber
150000 No more data is read or written.
This can have various causes:
The cable is defective.
The PLC does not respond, is defective, etc.
Connection made to the wrong interface.
The system is overloaded.
Check that the cable is plugged in,
the PLC is operational, the correct
interface is used.
Reboot the system if the system
message is displayed
continuously.
150001 Connection is re-established because the cause of
the interruption has been eliminated.
–
160000 No more data is read or written.
This can have various causes:
The cable is defective.
The PLC does not respond, is defective, etc.
Connection made to the wrong interfacet.
The system is overloaded.
Check that the cable is plugged in,
the PLC is operational, the correct
interface is used.
Reboot the system if the system
message is displayed
continuously.
160001 Connection is re-established because the cause of
the interruption has been eliminated.
–
170000
1)
S7 diagnostics messages are not displayed because
it is not possible to logon to the S7 diagnostics with
this unit. The service program is not supported.
–
170001
1)
The S7 diagnostics buffer cannot be displayed
because communication with the PLC has been
switched off.
Switch the PLC online.
170002
1)
The S7 diagnostics buffer cannot be displayed
because reading in the diagnostics buffer (SZL) was
terminated due to an error.
–
170003
1)
The display of an S7 diagnostics message is not
possible. An internal error %2 has been reported.
–
170004
1)
The display of an S7 diagnostics message is not
possible. An internal error with error class %2, error
number %3 has been reported.
–
170007
1)
It is not possible to read in the S7 diagnostics buffer
(SZL) because it was terminated with an internal error
with error class %2 and error code %3.
–
180000 A component/OCX receives configuration data with a
version identification which is not supported.
Install a newer component.
190000 It is possible that the tag will not be updated. –
190001 The tag is updated following an error status after the
cause of the last error state has been eliminated
(return to normal operation).
–
190002 The tag is not updated because communication to the
PLC has been switched off.
Switch on communication via the
function “Set Online”.
190004 The tag is not updated because the configured
address is not available for this tag .
Check the configuration.
190005 The tag is not updated because the configured PLC
type does not exist for this tag .
Check the configuration.